Explosion-proof Control stations HLBX03
Perhatian!
Spesifikasi Explosion-proof Control stations HLBX03
Application
Zone 1 and Zone 2
Zone 21 and Zone 22
Meet the necessities in the following industries, such as petroleum, chemical, electricity, medicine, textile, wine-making, aerospace, military, fire-fighting, etc.
Features
Features and benefits
◆ Explosion protection to
-CENELEC
-IEC
◆ GRP enclosure (glass fibre-reinforced polyester resin).
◆ Seven types of enclosure.
Catalogue number logic
Note:
1. Please refer to the Selection Table on P25.
2. Please select intermal components as below:
HL0101 explosion-proof control button selection table on P32/36
(nominal contact is 1NO+1NC);
HL0102 explosion-proof indicator switch selection table on P38/39;
HL0101-S explosion-proof control switch selection table on P34;
Explosion-proof ammeter / voltmeter.
3. Example: HLBX03-A2D2G
Components: Two control buttons, two indicators;surface type
Tech.Details: One start control button (HL0101-A1I02, 1NO+1NC);
One stop control button (HL0101-A1I22, 1NO+1NC);
One indicator (HL0102-G03, 230V AC);
One indicator (HL0102-R03, 230V AC);
4. Special requirements on request
echnical data
Explosion-proof control stations HLBX03(GRP)
Explosion protection | |
Gas explosion protection | II2 G Ex de IIC T6 Gb |
Dust explosion protection | II2 D Ex tb IIC T80℃ Gb ΙP66 |
Conformity to standards | EN 60079-0:2012,EN60079-1:2007,EN60079-7:2007,EN60079-31:2009 |
IEC 60079-0:2011,IEC60079-1:2007,IEC60079-7:2006,IEC60079-31:2008 | |
Enclosure Material | GRP(glass fibre-reinforced polyester resin) |
Enclosure colour | Black |
Exposed fastener | Stainless Steel |
Rated voltage | Max.415V AC |
Rated current | 6A |
Degree of protection | IP66 |
Ambient temperature | -40℃~+55℃ |
Components | 1.HL0101 explosion-proof control button technical data on P32/36; |
2.HL0102 explosion-proof indicator technical data on P38/39; | |
3.HL0101-S explosion-proof control switch technical data on P34; | |
4.Explosion-proof ammeter/voltmeter. | |
Cable entries | M□×1.5 plug |
Mounting | Surface type |
Pole type (for enclosure Ⅰ,Ⅱ,Ⅲ, Ⅳonly) | |
Note | 1.Please specify the number and size of entries (applicable for surface type only); |
2.For pole type,only G1" entry is applicable; |
Control station HLBX03(GRP) selection table
Dimension drawings (all dimension in mm) - subject to alteration
Dimension drawings (all dimension in mm) - subject to alteration
Operation head | h(mm) |
Frame | 11 |
Standard button | 18 |
Double button | 18 |
Button with key | 40 |
Emergency self-locked button | 40 |
Mushroom head button | 32 |
Mushroom head with key | 46 |
Signal lamp | 18 |
Button with lamp | 18 |
Control switch 1# | 29 |
Control switch 2#、3# | 32 |
-- | -- |